Equipment |
Typical CVD Control Settings |
|
(2) Group operated switches, any brand or configuration |
SW1 - Dry contact indication for valid fault 'event' if |
|
(2) SEECO motor operators |
current >= 1100 amps for 3 cycles AND potential is lost |
|
(4) SEECO current only sensors, type CS |
at 10 seconds |
|
(2) SEECO current and voltage sensors, type CSVS |
|
|
(2) SEECO local control logic devices, type CVD |
SW2 - Same as SW1 above |
|
|
|
|
Typical Breaker Timing |
|
|
20 cycles |
|
|
15 seconds |
|
|
60 seconds |
|
|
|
|
Note: the above breaker timing
and CVD control settings are for illustration purposes only; your application may have
values that are specific to your automation objectives and current
equipment settings |
|
|